防火卷簾門安裝維修后需及時進行功能測試
1、通電功能測試:將防火定州祈諾卷簾控制器分別與消防控制室的火災報警控制器或消防聯動控制設備、相關的火災探測器、卷門機等連接并通電,防火卷簾控制器應處于正常工作狀態;
1. Power on function test: connect and power on the fire prevention Dingzhou Qinuo roller shutter controller with the fire alarm controller or fire linkage control equipment in the fire control room, relevant fire detectors, door rolling machine, etc., and the fire prevention roller shutter controller should be in normal working state;
2、備用電源測試:設有備用電源的防火卷簾,其控制器應有主、備電源轉換功能。備用電源的電池容量應保證防火卷簾控制器在備用電源供電條件下能正常可靠工作1h,并應提供控制器控制卷門機速放控制裝置完成卷簾自重垂降,控制卷簾降下限位所需的電源;
2. Test of standby power supply: the controller of the fire shutter with standby power supply shall have the function of switching between main and standby power supply. The battery capacity of the standby power supply shall ensure that the fire shutter controller can work normally and reliably for 1H under the power supply condition of the standby power supply, and the power supply required for the controller to control the quick release control device of the door rolling machine to complete the self weight sag of the shutter and control the shutter to the lower limit shall be provided;
3、火災報警功能測試:防火卷簾控制器應直接或間接的接收來自火災探測器組發出的火災報警信號,并應發出聲、光報警信號;
3. Fire alarm function test: the fire shutter controller shall directly or indirectly receive the fire alarm signal from the fire detector group, and shall send audible and visual alarm signals;
4、故障報警功能測試:防火卷簾控制器的電源缺相或相序有誤,以及防火卷簾控制器與火災探測器之間的連接線斷線或發生故障,防火卷簾控制器均應發出故障報警信號;
4. Fault alarm function test: if the power supply of the fire shutter controller is out of phase or the phase sequence is wrong, and the connecting wire between the fire shutter controller and the fire detector is broken or malfunctioned, the fire shutter controller shall send out fault alarm signals;
5、自動控制功能調試:自動控制功能調試時,當防火卷簾控制器接收到火災報警信號后,應輸出控制防火卷簾完成相應動作的信號,并應符合下列要求:
5. Automatic control function debugging: when the automatic control function debugging, when the fire shutter controller receives the fire alarm signal, it should output the signal to control the fire shutter to complete the corresponding action, and should meet the following requirements:
1)控制分隔防火分區的防火卷簾由上限位自動關閉全閉;
1) Control the fire shutter separating the fire compartment to close automatically from the upper limit to the full close;
2)防火卷簾控制器接到感煙火災探測器的報警信號后,控制防火卷簾自動關閉中位(1.8m)處停止,接到感溫火災探測器的報警信號后,繼續關閉全閉;
2) After receiving the alarm signal from the smoke fire detector, the fire shutter controller controls the fire shutter to automatically close to the middle position (1.8m) and stop. After receiving the alarm signal from the temperature fire detector, it continues to close to the full close;
3)防火卷簾半降、全降的動作狀態信號應反饋到消防控制室
3) The action status signals of half lowering and full lowering of the fire shutter shall be fed back to the fire control room
6、手動控制功能測試:手動控制功能調試時,手動操作防火卷簾控制器上的按鈕和手動按鈕盒上的按鈕,可控制防火卷簾的上升、下降、停止;
6. Manual control function test: during manual control function commissioning, manually operate the button on the fire shutter controller and the button on the manual button box to control the rise, fall and stop of the fire shutter;
7、自重下降功能測試:自重下降功能調試時,應將
濟南防火卷簾門安裝維修機電源設置于故障狀態,防火卷簾應在防火卷簾控制器的控制下,依靠自重下降全閉。
7. Self weight lowering function test: during the self weight lowering function commissioning, the power supply of Jinan fire shutter door installation and maintenance machine should be set in the fault state, and the fire shutter should fall to fully closed by self weight under the control of the fire shutter controller.
The above is the relevant content of the question answer. I hope it can help you. If you still have any questions about this problem, you are welcome to follow our website //domachine.com.cn And consult our staff, will serve you wholeheartedly.